4" Magnetic Oil Level Gauge (MOG)

Magnetic Oil Level Gauge (MOG) is used to Measure Oil Level of oil filled Transformers & Oil filled Tanks.
  • No external power supply required for indication or operation
  • Sealed system which requires no trimming or periodic site adjustments
  • Directly Mounted on the Transformer & Other Process Control Equipments
Magnetic Oil Level Gauge (MOG) 4"

Magnetic Oil Level Gauge (MOG) is used to Measure Oil Level of oil filled Transformers & Oil filled Tanks

Dial size
100mm Round (Nominal)
Unit
Any calibration as per customer’s requirement is possible
Dial Color
Black marking on white background. Standard Red Line Indication for Min. to Empty Level
Spread
Max 300°
Material
Float & Float Arm are made of Brass
Float-Arm Length
Fixed Length as given by Customer
Travel
Max. 90° Below & Above center
Liquid in Tank
Transformer oil or any other Oil
Working Temperature
-30° to 100°C of oil
Working Pressure
0 to 4 KG/Cm2
Working Environment
Indoor or Outdoor
Mounting
The position can be selected on vertical wall of conservator/tank depending on importance of oil level reading and switching near Min. level.
Download PDF
Magnetic Oil Level Gauge (MOG) 4"
Switch Type
Micro switch
Contact Rating
5A @ 240V AC, 0.5A @ 220V DC
Switches
Normally Open Type (Changeover Type Optional)
Contact Type
Switch Contacts are Potential Free
All Line to Body (Earth) High Voltage Breakdown Tested
2 KV AC, 50 Hz. for 60 seconds
Terminal Type
WAGO Terminals – Press Fit Type