Search
ISO 9001:2008 Certificate From DNV - UKAS
High Performance and Credit Rating By NSIC , Dun & Bradstreet

News Updates

PRECIMEASURE Exhibiting its Products in AFRICA ELECTRICITY, 15-17 November 2011, Gallagher Convention Centre, Johannesburg, SOUTH AFRICA. STAND No.: D19

Electronic Type Instruments

Bearing Temperature Indicator: The Bearing Temperature Detector (BTD) measures the Temperature of the Bearings of Motors / Generators. It will display Bearing temperatures and take necessary control action as per set and differential values programmed by the user. The protection system also records maximum temperatures and will display the same along with corresponding channel number. Standard 4-20mA DC Signal Output and Optional RS-485 communication are available for connection to DAS / SCADA. Available up to 12 Channels.
Model 2412

RTD Based Digital Winding Temperature & Bearing Temperature monitoring and controlling device for Motor and Generator.


    This Scheme Consists of:

  • Pt-100 Sensors
  • Micro-controller based Temperature Scanner
  • Temperature Sensor
    RTD (Pt-100 DIN 43760)
    No. of sensor inputs
    Eight (Maximum)
    Range
    0-300°C
    Resolution
    0.1°C
    Accuracy
    ±1°C
    Display
    Six Seven Segment LEDs, Two for Channel Nos. and Four for displaying Temperature
    Display Speed
    User Settable (1-99 Seconds)
    Communication
    Isolated RS-485 MODBUS RTU Communication(Optional)
    Enclosure
    IP-55, Aluminum Pressure Die-casted, powder coated all side Enclosure with acrylic Viewing window
    Mounting
    Projection mounting with Anti–Vibration pads and M6 Screws (Flush Mounting Optional)
    Operating conditions
    Temp.: 0-60 Degree Centigrade. R.H. : 95% Max. non-condensing
    Download PDF
    Model 2412
    No. of Set-points
    Four Relay Outputs
    Contact Rating
    5A @220V AC / 5A@30V DC
    Switch Contact Type
    1 Changeover SPDT Relay Contacts
    Supply Voltage
    90-260 V AC/DC (Other voltages on Request)
    Terminals
    Suitable for 2.5 sq.mm. wire
    Analogue Outputs
    4-20mA DC (Maximum burden 600 Ohms)
    Power Consumption
    5 Watts
    Insulation Resistance
    IR More than100Mohm when measured with 500V DC Megger
    High Voltage
    2KV RMS at 50/60 Hz for1minute, Between All Terminals to Earth